203
DM Area Allocations (Using Serial Gateway Mode)
Section 6-2
■
Details
Port Settings
Set whether to make the user-specified settings for port 1 or port 1. These
settings are the same as for the RS-232C port of general-purpose external
devices connected using a protocol macro.
0: Default; 1: User-specified setting
When the default (0) is set, the following details are set for the port and bits 00
to 04 do not need to be set separately.
Baud rate: 9,600 bps; Start bits: 1 bit; Data length: 7 bits; Parity: Even; Stop
bits: 2 bits
When user-specified settings (1) are specified, set bits 00 to 04 and the baud
rate (in the following word).
Setting example: 0900 hex: Serial Gateway mode, using default settings for
port setting and baud rate.
Serial Communications Mode
Serial Gateway mode is used, so set to 9 hex.
Start Bits, Data Length, Stop Bits, Parity, Baud Rate
Set these bits if the port setting is set to user-specified settings. The start bit is
always 1 bit (1) regardless of which value is set. Do not set the baud rate
between B and F hex. Doing so will result in a system error and operation will
proceed using the default (9,600 bps). Do not set 1 or 2 hex, which are
reserved for the system.
User-specified Send Delay Time
After the FINS command is received by the Board/Unit and converted into the
specified protocol, it is not transferred immediately, but sent after the delay
time set within the following range
0000 to 7530 hex (0 to 30,000 decimal) (unit: 10 ms): 0 to 300 s (0 to
300,000 ms)
D32001
D32011
m+1
m+11
04 to 15
Reserved
00 to 03
Baud rate (unit: bps)
0 hex: 9,600 (default); 3 hex: 1,200; 4 hex: 2,400; 5 hex: 4,800;
6 hex: 9,600; 7 hex: 19,200; 8 hex: 38,400; 9 hex: 57,600; A hex:
115,200
D32002
D32012
m+2
m+12
15
Send delay
0: default (0 ms); 1: User-specified
00 to 14
Send delay setting range: 0 to 399 s (0 to 300,000 ms)
0000 to 7530 hex (0 to 30,000 decimal) (Unit: 10 ms)
D32003
D32013
m+3
m+13
15
CTS control
0: No; 1: Yes
D32007
D32017
m+7
m+17
08 to 15
Serial Gateway response timeout monitoring time
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s (Unit: 100 ms)
00 to 07
Serial Gateway send start timeout monitoring time
(only protocol macro mode)
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s (Unit: 100 ms)
DM Area
Bit
Setting
Board (CS Series
only)
Unit (CS/CJ
Series)
Port 1
Port 2
Port 1
Port 2
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...