222
Protocol Conversion
Section 6-5
Use the following method to access the serially (serial-to-serial) connected
PLC from the CX-Programmer.
1,2,3...
1.
Register the PLC to be connected serially (using Host Link FINS) in the
project gateway (e.g., PLC2).
2.
In the Change PLC Dialog Box of the target PLC (e.g., PLC1), select the
relay PLC (gateway PLC) in the Network Type
pull-down menu (e.g.,
[PLC2] (See note.)) and click the
Settings
Button to the right of the Net-
work Type
pull-down menu
.
Note
The PLC name enclosed in square brackets (e.g., [PLC2]) indicates
the gateway PLC.
3.
The Network Settings Dialog Box will be displayed. Click the
Guide for Se-
rial Gateway
Button.
4.
The
Serial Gateway Guide
Dialog Box will be displayed.
Select the unit and the port number under the
Calculate Address Area
, the
serial port number address is automatically calculated in the
Calculated
Address Field
.
Select the
Use SYSWAY with the port
option, and enter the actual Host
Link unit number for the target (communications partner) PLC in the
Host
Link Unit Number field
(see note).
Finally, click the
Apply
Button.
System Configuration Example
PLC name: PLC2
CX-Programmer Ver. 5.0 or later
Network type: Select
[PLC2]
.
Host Link FINS
PLC name: PLC1
Target PLC Host Link unit number
Set the relay PLC.
(Select in the Change PLC Dialog Box.)
Serial Communications Board/Unit with unit Ver. 1.2 or later
(Select
SCU (Unit 0 to 15)
in the
UNIT
field.)
Serial Gateway function
port (Select port 1/2 in the
PORT
field according to
the calculated address.)
Serial
Gate-
way
Select the
Use SYSWAY with the port
option
in the Host Link (SYSWAY) settings.
Enter the Host Link unit number in the
Host Link Unit Number
field for the target
PLC in the Host Link (SYSWAY) settings.
Select the PLC to be used as the
relay PLC (e.g., [PLC2]) in the
Network Type pull-down menu.
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...