419
Host Link FINS Command Master
Appendix D
Command Frame Contents
Response Frame Contents
Item
Contents
@
The @ symbol is automatically attached to the beginning of the command.
Host Link unit
number
Specify the unit number for Host Link between 0 and 31 BCD.
Command code
Specify a 2-character code. Always set “FA” (ASCII: 46, 41) when sending FINS commands. In this
protocol, “FA” is automatically generated.
Response wait
time
The response wait time sets the time from when the CPU Unit receives a command block until it
starts to return a response. This time is automatically set to “0” (ASCII: 30).
ICF (Information
control field)
Specify whether or not there are network relays. ICF is automatically set to “80” (ASCII: 38,30) indi-
cating that network relays are used.
RSV (Reserved)
RSV is automatically set to “00” (ASCII: 30,30). Setting RSV is required only when sending to a CPU
Unit on a network.
GCT (Gateway
count)
This is the number of networks through which the transmission can be relayed. “02” (ASCII: 30,32) is
automatically generated.
DNA (Destination
network address)
DA1 (Destination
node address)
DA2 (Destination
unit address)
Specify the network, node, and unit addresses of the remote destination node.
DNA (Destination Network Address)
Set between 00 and 7F Hex (0 and 127 decimal). The network address (DNA) setting is required to
specify the node address on the specified network.
DA1 (Destination Node Address)
Set in hexadecimal. The setting range depends on the network type. Set to 00 hex as the local node
when sending commands to a PLC slave directly connected using serial communications.
DA2 (Destination Unit Address)
Set the address of the device on the FINS network (e.g., CPU Unit, Special I/O Unit, personal com-
puter).
CPU Unit: 00 hex
CPU Bus Unit: Unit 10 hex
Example: Set 13 hex for unit number 3.
Special I/O Unit (except C200H Special I/O Units): Unit 20 hex
Example: Set 23 hex for unit number 3.
SNA (Source net-
work address)
SA1 (Source node
address)
Specify the source network and node addresses. These settings are set to “00” (ASCII: 30, 30)
regardless of whether or not there is a network relay.
SA2 (Source unit
address)
Specify the unit address of the unit at the PLC slave that is connected to the PLC master. SA2 is
automatically set to “00” (ASCII: 30, 30) to indicate the CPU Unit. When “00” is set, internal process-
ing converts the value to the unit address of each serial port.
SID (Service ID)
The SID is used as a counter when resending. It is automatically set to “55” (ASCII: 35, 35).
Command code,
text
Set the command code and text according to the FINS command and response formats.
FCS (frame check
sequence)
A 2-character FCS is automatically set.
Terminator
The terminator is a required delimiter at the end of a command. The terminator is automatically set
to
*
CR (ASCII: 2A, 0D).
Item
Contents
@
The @ symbol is automatically attached to the beginning of the response.
Host Link unit num-
ber, header code
The same unit number and header code specified in the FINS command that was received will be
returned.
ICF (Information
control field)
For a CPU Unit on a network, “C0” (ASCII: 43, 30) will be returned.
RSV (Reserved)
This section is reserved for the system. Set “00” (ASCII: 30,30).
GCT (Gateway
count)
The same GCT that was specified in the command that was received will be returned.
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...