Using the Serial Gateway
Section 6-4
6-4
Using the Serial Gateway
Use of the Serial Gateway basically requires only the DM Area (Setup Area)
and CIO Area settings.
Note
If routing tables are required, set them using the CX-Net.
Step 1: Set the DM Area (Setup Area) and CIO Area.
Using Serial Gateway Alone
• DM Area (Setup Area) Settings
m = 100
×
unit number
1908
1918
n+8
n+18
15
Transmis-
sion error
status
1: Transmission error; 0: No transmission error
08 to 14
Not used
07
1: FCS check error (transmission path error); 0: FCS check
normal
06
Not used
05
1: Serial Gateway send start timeout or Serial Gateway
response timeout
0: Normal
04
1: Overrun error (see note 7); 0: Normal
03
1: Framing error (see note 8); 0: Normal
02
1: Parity error (see note 8); 0: Normal
00, 01
Reserved
Words
Bit
Contents
Board
(CS Series
only)
Unit
(CS/CJ Series)
Port 1
Port 2
Port 1
Port 2
Words
Bit
Setting contents
Board
Unit
Port 1
Port 2
Port 1
Port 2
D32000
D32010
m
m+10
08 to 11
Serial communications mode
9 hex: Serial Gateway mode
00 to 04
Communications conditions
including start bits, data
length, stop bits, parity (set to
match the protocol at the
conversion destination)
D32002
D32012
m+2
m+12
15
Send delay
0: Default (0 ms)
1: User-specified
00 to 14
User-specified send delay
0 to 300 s (0 to 300,000 ms):
0000 to 7530 hex (0 to
30,000 decimal)
(Unit: 10 ms)
D32003
D32013
m+3
m+13
15
CTS control
0: No; 1: Yes
D32007
D32017
m+7
m+17
08 to 15
Response timeout monitoring
time
00 hex: 5 s (default)
01 to FF hex (1 to 255 deci-
mal): 0.1 to 25.5 s
(Unit: 100 ms)
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...