160
Auxiliary Area and CIO Area Allocations
Section 5-3
Note
These bits are used both to change the port settings and to restart the port at
the same time. One of these bits can be turned ON to restart a port without
changing the port settings in the Setup Area allocated in the DM Area. The
STUP(237) instruction can also be used to just restart a communications port
by executing STUP(237) with the same port settings as the ones already
being used.
Serial Communications Boards (CS Series Only)
Serial Communications Boards (CS/CJ Series)
n = A620 + unit number
Inner Board Error
Information (CS-series
Serial Communications
Board Only)
A424 contains error information for the Serial Communications Board.
Note
1.
When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag)
(non-fatal error) will be ON.
2.
When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON.
For details on errors, refer to
SECTION 11 Troubleshooting and Maintenance
Word
Bit
Contents
A636
03 to 15
Reserved
02
1: Port 2 Settings Change Bit
01
1: Port 1 Settings Change Bit
00
Reserved
Words
Bit
Contents
n
03 to 15
Reserved
02
1: Port 2 Settings Change Bit
01
1: Port 1 Settings Change Bit
00
Reserved
Word
Bit
Contents
A424
12 to 15
Non-fatal
errors
(Note 1)
Reserved
11
1 Error log EEPROM error; 0: Normal
10
1: Protocol macro execution error; 0: Normal
This bit will be turned ON when code 3 or 4 is stored
in the error code for bits 00 to 03 of CIO 1909 or CIO
1919 in the CIO Area.
09
1: Protocol data error (SUM error); 0: Normal
08
1: Setup error; 0: Normal
07
1: Routing table error; 0: Normal
06
Reserved
05
1: Cyclic monitoring error; 0: Normal
04
Reserved
03
Fatal
errors
(Note 2)
Reserved
02
Reserved
01
1: Inner Bus error; 0: Normal
00
1: Inner Board watchdog timer error; 0: Normal
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...