Communications Frames
Section 6-8
List of Settings
• FINS Network Settings
• Modbus-RTU Settings
Command Frame
2804
FINS header
Network (Ethernet)
FINS message
Modbus-RTU command
FINS message
Network (Controller Link)
Network address: 2
Serial Communications Unit
Unit No. 3, port 1
Conversion Link Unit
Node address: 5
Port 1 unit address:
80 hex + 4 hex
×
unit number 3 = 8C hex
RS-485 (Modbus-RTU)
3G3MV OMRON Inverter
CPU Unit
CMND
instruction
FINS header
2804
Modbus-RTU command
Protocol
conversion
Modbus-RTU command
Example: Write data for frequency reference value
(FUNCTION code 10 hex, register No. 0002 hex)
Item
Value
(Example)
Setting location
Send destination network address
(Controller Link network address of PLC
to which Serial Communications Unit is
mounted)
2
Set 02 hex in the control data C+2 bits 00 to 07 (net-
work address) of CMND(490).
Note: Set 0 hex in the control data C+2 bits 08 to 11
(serial port number) of CMND(490).
Send destination node address
(node address in Controller Link for PLC
to which Serial Communications Unit is
mounted)
5
Set 05 hex in the control data C+3 bits 08 to 15 (send
destination node address) of CMND(490).
Serial Communications Unit unit num-
ber
3
Use to calculate the following unit address for the
serial port
80 hex + 4 hex
×
unit number 3 = 8C hex
Serial Communications Unit serial port
Port 1
Send destination unit address
(unit address of serial port on Serial
Communications Unit)
80 hex + 4 hex
×
unit
number 3 = 8C hex (or
10 + unit number 3 = 13
hex, and serial port
number 1 = 1 hex)
Set 8C hex in the control data C+3 bits 00 to 07 (send
destination unit address) of CMND(490).
(Alternatively, set 13 hex in the control data C+3 bits
00 to 07 (send destination unit address) and set 1 hex
in C+2 bits 08 to 11 (serial port number).)
Item
Set
value
Setting location
FINS command code: Converting
to Modbus-RTU = 2804 hex
2804
hex
Set 2804 hex in controller data s of the
CMND(490) instruction.
Modbus slave address (e.g., 02
hex)
02
hex
Set 0210 hex in controller data s+1 of
the CMND(490) instruction.
FUNCTION code: DATA WRITE =
10 hex
10
hex
Write data register No. (e.g., fre-
quency reference = 0002 hex)
0002
hex
Set 0002 hex in controller data s+2 of
CMND(490).
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...