453
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Bit Data (T/C Device Type)
(Sequence No. 807 (Hex 0327)) (Command Code: BR)
This sequence reads the bit (PV) data for the number of device points starting from the specified device
address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station
number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the
specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits hex)
Always 0005 hex (5 decimal)
+1
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
+2
Device type (4 digits hex)
Set the device type (2 characters) in
ASCII.
+3
(Undefined) Device
No.
(3 digits hex)
Set the first read address of the device
to read.
+4
(Undefined) Device
words/
bits
(2 digits hex)
Set the number of device words/bits to
read.
+0
+1
+2
+3
+4
(Undefined)
Number of send data words
PLC No.
Station No.
Device type
(Undefined)
Device No.
First word of
send data
Number of device
words/bits
Offset
Contents (data format)
Data
+0
Number of receive data words
0003 to 00FA hex (3 to 250 decimal)
+1
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
+2
Read data (4 digits hex)
Stores the number read data converted
into hexadecimal.
Receive data
storage words
Number of receive data words
+0
+1
PLC No.
+2
Station No.
Read data
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...