178
Using Protocol Macros
Section 5-4
Flags
Operand Areas and Address Ranges
Note
The EM Area cannot be specified for the receive data when the interrupt noti-
fication function is being used for a Serial Communications Board. If the EM
Area is specified, a protocol macro syntax error will occur and A42410 will
turn ON.
Name
Label
ON
OFF
Error Flag
ER
• The
Communications Port Enabled
Flag for the specified communica-
tions port (internal logical port) was
OFF when the instruction was exe-
cuted.
• The specified serial port (physical
port) is not set to protocol macro
mode.
• The data setting in C1 is not within
the allowed range.
• The number of words specified in S
or D exceeds 249 (when a word
address was specified for S or D).
All other cases
Access Error Flag AER
A read/write-protected area was
specified for send data or receive
data.
A write-protected area was specified
for receive data.
All other cases
Area
C1
C2
S
R
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Area
H000 to H511
Auxiliary Area
A000 to A959
A448 to A959
Timer Area
T0000 to T4095
---
Counter Area
C0000 to C4095
---
Data Memory (DM) Area
D00000 to D32767
Extended Data Memory (EM) Area
E00000 to E32767
(see note)
Extended Data Memory (EM) Area
(including bank specification)
En_00000 to En_32767 (n = 0 to C)
(see note)
Indirect DM/EM address, Binary
@D00000 to @32767, @E00000 to @E32767,
@En_00000 to @En_32767
(see note)
Indirect DM/EM address, BCD
*D00000 to *D32767, *E00000 to *E32767,
*En_00000 to *En_32767
(see note)
Constant Area
See
Control Data 1
(C1)
.
0000 to 037E Hex
(0 to 999)
#0000 to FFFF
(Binary data)
Data Registers
DR0 to DR15
---
Index Registers, direct
---
Index Registers, indirect
,IR0 to ,IR15
-2048 to +2047,IR0 to -2048 to +2047,IR15
DR0 to DR15,IR0 to IR15
,IR0+(++) to ,IR15+(++)
,-(- -)IR0 to ,-(- -)IR15
(see note)
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...