![Omron SYSMAC CJ1W-SCU21-V1 Operation Manual Download Page 595](http://html1.mh-extra.com/html/omron/sysmac-cj1w-scu21-v1/sysmac-cj1w-scu21-v1_operation-manual_743586595.webp)
566
ES100
@
Digital Controller Protocol
Appendix K
Read Heater Burnout Data (Sequence No. 253 (Hex 00FD))
Reads the heater burnout alarm in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
•
•
+128
(max.)
16th unit
Error group 14 data (2 digits Hex)
Error group 15 data (2 digits Hex)
00 to FF
00 to FF
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
Number of units + 2
+1
Number of units (4 digits Hex)
0001 to 0020 (1 to 32 decimal)
+2 1st
unit
Unit No. (2 digits BCD)
00 to 31
+3
2nd unit
Unit No. (2 digits BCD)
00 to 31
•
•
•
+33
(max.)
32nd unit
Unit No. (2 digits BCD)
00 to 31
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
Number of units +1
+1
1st unit
Heater burnout alarm (2 digits Hex)
00 to FF
+2
2nd unit
Heater burnout alarm (2 digits Hex)
00 to FF
+3
3rd unit
Heater burnout alarm (2 digits Hex)
00 to FF
+4
4th unit
Heater burnout alarm (2 digits Hex)
00 to FF
•
•
•
+32
(max.)
32nd unit
Heater burnout alarm (2 digits Hex)
00 to FF
Offset
Contents (data format)
Data
(Undefined)
Unit No.
First word of
send data
Number of send data words
+0
+1
+2
+3
+33
(Undefined)
Unit No.
Number of units
(Undefined)
Unit No.
~
~
32nd unit (max.)
2nd unit
1st unit
(Undefined)
Heater burnout alarm
Receive data
storage words
Number of receive data words
+0
+1
+2
+3
+4
+32
(Undefined)
Heater burnout alarm
(Undefined)
Heater burnout alarm
~
~
32nd unit (max.)
3rd unit
2nd unit
(Undefined)
Heater burnout alarm
1st unit
(Undefined)
Heater burnout alarm
4th unit
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...