83
I/O Memory Allocations
Section 2-3
Protocol Macro Mode
n = CIO 1500 + 25
×
unit number
NT Links
n = CIO 1500 + 25
×
unit number
Words
Bit
Contents
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1
Port 2
Port 1
Port 2
CIO
1909
CIO
1919
n + 9
n + 19
15
Port
operat-
ing sta-
tus
Protocol Macro Executing Flag
14
Step Troubleshooting Flag
13
Aborted Flag
12
Tracing Flag
11
Sequence End Completion Flag
10
Sequence Abort Completion Flag
09
Sequence Waiting Flag
08
Serial Gateway Prohibited Flag
1: Prohibited; 0: Not prohibited
04 to 07
Reserved
00 to 03
Error codes
0: No error
2: Sequence number error
3: Data read/write area exceeded error
4: Protocol data syntax error
CIO
1910
CIO
1920
n + 10
n + 20
12 to 15
Reserved
00 to 11
Communications Sequence Number
000 to 999 (000 to 3E7 hex)
CIO
1911
CIO
1921
n + 11
n + 21
12 to 15
Reserved
08 to 11
Executed Step Number (code)
0 to 15 (0 to F hex)
04 to 07
Reserved
00 to 03
Executed Reception Case Number (code)
0 to 15 (0 to F hex)
CIO
1912
CIO
1922
n + 12
n + 22
00 to 15
Executed Reception Case Number Storage Flag
0 to 15: Correspond to bits 00 to 15
CIO
1913
CIO
1923
n + 13
n + 23
00 to 15
Executed Step Number Storage Flag
0 to 15: Correspond to bits 00 to 15
CIO
1914
CIO
1924
n + 14
n + 24
08 to 15
Repeat Counter Setting Value
0 to 255 (00 to FF hex)
00 to 07
Repeat Counter Present Value
0 to 255 (00 to FF hex)
Words
Bit
Contents
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1
Port 2
Port 1
Port 2
CIO
1909
CIO
1919
n + 9
n + 19
08 to 15
PT Priority Registered Flag
00 to 07
PT Communications Flag
CIO
1910 to
CIO
1914
CIO
1920 to
CIO
1924
n + 10 to
n + 14
n + 20 to
n + 24
00 to 15
Reserved
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...