![Omron SYSMAC CJ1W-SCU21-V1 Operation Manual Download Page 475](http://html1.mh-extra.com/html/omron/sysmac-cj1w-scu21-v1/sysmac-cj1w-scu21-v1_operation-manual_743586475.webp)
446
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
• Sending Commands Common to ACPU
The values in parentheses are hexadecimal.
Send/Receive User-specified Computer Link Commands, with ASCII
Conversion
(Sequence No. 800 (Hex 0320)) Command Code: User-specified
This sequence converts the text data of a user-specified Computer Link command into ASCII and sends to the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows). The
response data is converted into hexadecimal and stored in the CS/CJ-series CPU Unit starting from the speci-
fied word.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Sequence
No.
Communications
sequence name
Computer Link
command
Function
818 (0332) Loopback test
TT (Loopback
test)
Executes a loopback test at the Mitsubishi Computer Link Module
with the specified station number (and the PLC number that fol-
lows). (E.g, if the data starting from the specified word + 3 is sent
from the host, the Computer Link Module will return the data
unchanged to the host.)
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits hex)
0004 to 00FA hex (4 to 250 decimal)
+1
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
+2
Command (4 digits hex)
Specify the service command code to
be used in ASCII.
+3
Number of send bytes
(4 digits hex)
0000 to 007A hex (0 to 122 decimal)
Specify the number of text data bytes
for the communications line (i.e., twice
the number of text bytes in S+4
onwards)
+4
Text data
Set the text data for the command. The
specified hexadecimal data will be con-
verted into ASCII and sent.
Number of send bytes
Number of send data words
+0
+1
+2
PLC No.
+3
+4
Station No.
Command
Text data
First word of
send data
Offset
Contents (data format)
Data
+0
Number of receive data bytes
0002 to 00FA hex (2 to 250 decimal)
+1
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Station No: 00 to FF hex
PLC No.: 00 to FF hex
+2
Receive data (4 digits hex)
Any receive data is converted into
hexadecimal and stored.
Receive data
storage words
Number of receive data words
+0
+1
PLC No.
+2
Station No.
Receive data
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...