296
Changes from Previous Products
Section 9-5
Unit (CS1H/G-CPU
@@
RS-232C port, CS1W-SCU21-V1 ports, CJ1W-
SCU21/41 port 2, CS1W-SCB21-V1 ports, or CS1W-SCB41-V1 port 1).
Previous
products
Model number
Changes required for CS/CJ-series product
Wiring
Other
C-series Mod-
bus-RTU Slave
Units
3G2A5-LK201-E
C500-LK203
3G2A6-LK201-E
The connector has been
changed from a 25-pin to a
9-pin connector.
The CS/CJ-series products
do not support the ST1, ST2,
and RT signals and wiring
them is not required.
The following changes are necessary for
systems that sync with ST1, ST2, and RT.
Synchronized transfers will no longer be possi-
ble.
Full-duplex transmissions will be possible with
the CS/CJ-series product, but the host com-
puter’s communications program, hardware, or
both will need to be altered.
The following changes are necessary for
systems that did not sync with ST1, ST2,
and RT.
It may be possible to use the host computer
programs without alteration as long as the
same communications settings (e.g., baud rate)
are used. It may be necessary, however, to
change programs to allow for different text
lengths in frames or different CS/CJ command
specifications. (See note.)
C200H-LK201
The connector has been
changed from a 25-pin to a
9-pin connector.
It may be possible to use the host computer
programs without alteration as long as the
same communications settings (e.g., baud rate)
are used. It may be necessary, however, to
change programs to allow for different text
lengths in frames or different CS/CJ command
specifications. (See note.)
C-series CPU
Units
SRM1
CPM1
CPM1A
CQM1-CPU
@@
-E
C200HS-CPU
@@
-E
C200HX/HG/HE-
CPU
@@
-E
C200HW-COM
@@
-E
No changes have been made
in wiring.
It may be possible to use the host computer
programs without alteration as long as the
same communications settings (e.g., baud rate)
are used. It may be necessary, however, to
change programs to allow for different CS/CJ
command specifications.
CVM1 or CV-
series CPU
Units
CVM1/CV-CPU
@@
No changes have been made
in wiring.
It may be possible to use the host computer
programs without alteration as long as the
same communications settings (e.g., baud rate)
are used. It may be necessary, however, to
change programs to allow for different CS/CJ
command specifications.
CVM1 or CV-
series Modbus-
RTU Slave Unit
CV500-LK201
Port 1:
The connector has been
changed from a 25-pin to a
9-pin connector.
Port 2 set for RS-232C:
The SG signal has been
changed from pin 7 to pin 9.
The following changes are necessary for
half-duplex transmissions that use CD.
Check the system for timing problems when
using SEND, RECV, or CMND to initiate com-
munications from the PLC or timing problems in
sending commands from the host computer. If
necessary, switch to full-duplex transmissions.
The following changes are necessary for
full-duplex transmissions that do not use
CD.
Half-duplex It may be possible to use the host
computer programs without alteration as long
as the same communications settings (e.g.,
baud rate) are used. It may be necessary, how-
ever, to change programs to allow for different
CS/CJ command specifications.
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...