Specifications
Section 1-6
Note
1.
The baud rate and the communications distance sometimes depend on the
remote device.
2.
A macro syntax error will occur if the interrupt notification method is exe-
cuted for a Serial Communications Unit.
3.
When using 2-wire RS-422A/485 communications in Protocol Macro
Mode, set only modem controls for the send control parameters, and do
not use RS/CS flow controls.
Step contents
Commands
Send only (SEND), receive only (RECV), send and receive
(SEND&RECV), wait (WAIT), reception buffer clear (FLUSH), ER-ON
(OPEN), or ER-OFF (CLOSE)
Repeat counter
1 to 255 times
Retry count
0 to 9
(Only when the command is SEND&RECV)
Send wait time
0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 minutes
(Only when the command is SEND or SEND&RECV)
With or without
response write
(operand)
When receive processing is completed (when the receive data is stored
in the area specified in the 4th operand of the PMCR(260) instruction),
whether or not to store the received messages can be selected.
Next processing
When a step has ended normally, End (sequence completed), Next (pro-
ceed to the next step No.), Goto (go to the specified step No.), or Abort
(interrupt the step and terminate that sequence) can be selected.
Error processing
When a step has ended abnormally, End, Next, Goto, or Abort can be
selected.
Send message
Data sent to the
specified address
when the command
is SEND or
SEND&RECV.
Consists of a header (*1), address (*2), length,
data (*2), error check code (*3), and terminator
(*1).
For an explanation of *1, *2, and *3, see the next
page.
Receive message
Data sent from the
specified address
when the command
is RECV or
SEND&RECV.
Reception matrix
When the command
is RECV or
SEND&RECV, sets
the expected
receive messages
(15 max.), and
switches to the next
processing accord-
ing to the message
received.
Specifies the receive messages and the next pro-
cessing for each of cases No. 00 to No. 15. Of the
maximum 16 cases, one case must be set as
“Other” in the receive messages (in addition to the
set receive messages).
Item
Description
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...