423
Host Link FINS Command Master
Appendix D
FINS COMMAND SEND/RECEIVE
(Sequence No. 750 (Hex 02EE)
This sequence sends user-specified FINS commands to the specified Host Link Unit and stores the response
starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits hex)
0005 to 00FA hex (5 to 250 decimal)
+1
Host Link unit
No.
(2 digits BCD)
Remote destina-
tion network
address (DNA)
(2 digits hex)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
+2
Remote destina-
tion node
address (DA1)
(2 digits hex)
Remote destina-
tion unit address
(DA2)
(2 digits hex)
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
+3
MRC
(2 digits hex)
SRC
(2 digits hex)
User-specified FINS command
+4
Number of FINS text bytes
(4 digits hex)
0000 to 03D4 hex
Specify the number of FINS command
text bytes for the communications line
(i.e., twice the number of bytes of FINS
text in S+5 onwards)
+5
FINS text
The text for the user-specified FINS
command to send.
FINS text
Number of send data words
+0
+1
+2
+5
+3
MRC
+4
Number of FINS text bytes
Host Link unit number
Remote destination node
address (DA1)
SRC
Remote destination
network address (DNA)
Remote destination unit
address (DA2)
First word of
send data
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits hex)
0002 to 00FA hex (2 to 250 decimal)
+1
End code (4 digits hex)
The end code is stored in hexadecimal.
+2
FINS receive text
The received text is stored.
FINS receive text
Receive data
storage words
Number of receive data words
+0
+2
+1
End code
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...