8 CONTROL SUB FUNCTIONS
8.8 Functions Related to Stop
277
8
Step function settings
To use the "step function", write the data shown in the following table to the Simple Motion module using the program. Refer to
the following for the timing of the settings.
Page 275 Using the step operation
The set details are validated after they are written to the Simple Motion module.
n: Axis No. - 1
Refer to the following for the setting details.
Setting item
Setting
value
Setting details
Buffer memory address
[Cd.34]
Step mode
Set "0: Stepping by deceleration units" or "1: Stepping by data No. units".
4344+100n
[Cd.35]
Step valid flag
1
Set "1: Validates step operations".
4345+100n
[Cd.36]
Step start information
Set "1: Continues step operation", depending on the stop status.
4346+100n
Summary of Contents for RD77MS16
Page 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Page 2: ......
Page 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Page 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Page 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Page 643: ......