310
9 COMMON FUNCTIONS
9.4 External Input Signal Select Function
■
External input signals from the servo amplifier and buffer memory (upper/lower stroke limit
signal (FLS/RLS), near-point dog signal (DOG), and stop signal (STOP))
Use the following parameter to switch the logic of the external input signals from the servo amplifier and buffer memory
(upper/lower stroke limit signal (FLS/RLS), near-point dog signal (DOG), and stop signal (STOP)).
Refer to the following for the setting details.
■
External input signals from the external device connected with the Simple Motion module
(upper/lower stroke limit signal (FLS/RLS), near-point dog signal (DOG), stop signal (STOP),
and external command signal/switching signal (DI))
Use the following parameter to switch the logic of the external input signals from the external device connected with the
Simple Motion module (upper/lower stroke limit signal (FLS/RLS), near-point dog signal (DOG), stop signal (STOP), and
external command signal/switching signal (DI)).
Refer to the following for the setting details.
■
Manual pulse generator/Incremental synchronous encoder input
Use the following parameter to switch the external input signal logic for the manual pulse generator/incremental synchronous
encoder.
Refer to the following for the setting details.
Input type of "[Pr.116] FLS signal selection"
to "[Pr.119] STOP signal selection"
Signal type
Setting area
0: Simple Motion module
FLS/RLS/DOG/STOP/DI
[Pr.150] Input terminal logic selection
Manual pulse generator
[Pr.151] Manual pulse generator/Incremental synchronous
encoder input logic selection
1: Servo amplifier
FLS/RLS/DOG
[Pr.22] Input signal logic selection
2: Buffer memory
FLS/RLS/DOG/STOP
Setting item
Initial value
Setting details
[Pr.22]
Input signal logic selection
Select the logic of the signal which is input to the Simple Motion module from the
external device.
0: Negative
logic
1: Positive
logic
(Always "0" is set to the part not used.)
Setting item
Initial value
Setting details
[Pr.150]
Input terminal logic selection
0
Select the logic for the input signal from the external device connected with the Simple
Motion module.
0: ON at leading edge
(When the current is flowed through the input signal terminal: ON,
When the current is not flowed through the input signal terminal: OFF)
1: ON at trailing edge
(When the current is flowed through the input signal terminal: OFF,
When the current is not flowed through the input signal terminal: ON)
[Input terminal range]
RD77MS2: b0 to b9
RD77MS4/RD77MS8/RD77MS16: b0 to b19
Setting item
Initial value
Setting details
[Pr.151]
Manual pulse generator/
Incremental synchronous encoder
input logic selection
0
Select the input signal logic to the Simple Motion module from the manual pulse
generator/incremental synchronous encoder.
0: Negative
logic
1: Positive
logic
Summary of Contents for RD77MS16
Page 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Page 2: ......
Page 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Page 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Page 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Page 643: ......