APPENDICES APPENDIX
Appendix 3 Compatible Devices with SSCNETIII(/H)
629
A
■
Reset selection/disconnected PU detection/PU stop selection
When PU stop is executed in FR-A700 series, position error excessive, etc. occur because a command from Simple Motion
module does not stop. Set "0 to 3" in the parameter of the inverter "[Pr.75] Reset selection/ disconnected PU detection/PU
stop selection". To stop FR-A700 series, use the stop signal and the forced stop of Simple Motion module, or use the output
stop (MRS) of FR-A700 series.
*1
Note that the default value is set to "14". (Change the value to "0 to 3".)
■
In-position range
Set the servo parameter "In-position range (PA10)" and the parameter of the inverter "[Pr.426] In-position width" to be
matched. Otherwise, it may not operate correctly.
n: Axis No. - 1
Setting item
Default
value
Setting
value
Details
[Pr.75]
Reset selection/disconnected PU detection/
PU stop selection
14
0
• Reset input is always enabled.
• If the PU is disconnected, operation will be continued.
• PU stop is disabled at SSCNET
connection.
1
• A reset can be input only when the protective function is activated.
• If the PU is disconnected, operation will be continued.
• PU stop is disabled at SSCNET
connection.
2
• Reset input is always enabled.
• When the PU is disconnected, the inverter trips.
• PU stop is disabled at SSCNET
connection.
3
• A reset can be input only when the protective function is activated.
• When the PU is disconnected, the inverter trips.
• PU stop is disabled at SSCNET
connection.
14
• Reset input is always enabled.
• If the PU is disconnected, operation will be continued.
• Deceleration stop by PU stop in any operation mode.
15
• A reset can be input only when the protective function is activated.
• If the PU is disconnected, operation will be continued.
• Deceleration stop by PU stop in any operation mode.
16
• Reset input is always enabled.
• When the PU is disconnected, the inverter trips.
• Deceleration stop by PU stop in any operation mode.
17
• A reset can be input only when the protective function is activated.
• When the PU is disconnected, the inverter trips.
• Deceleration stop by PU stop in any operation mode.
Setting item
Default value
Setting range
Buffer memory address
PA10
In-position range
100 (pulse)
0 to 65535 (pulse)
28410+100n
Setting item
Default value
Setting range
Details
[Pr.426]
In-position width
100 (pulse)
0 to 32767 (pulse)
When droop pulses have fallen below the setting value, the in-position
signal turns ON.
Summary of Contents for RD77MS16
Page 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Page 2: ......
Page 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Page 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Page 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Page 643: ......