9 COMMON FUNCTIONS
9.12 Connect/Disconnect Function of SSCNET Communication
347
9
Program
The following shows the program example to connect/disconnect the servo amplifiers connected after Axis 5.
■
Disconnect operation
Disconnect procedure
Connect procedure
Turn OFF the servo amplifier's power supply after checking the LED display
"AA" of servo amplifier by turning bDisconnectCommand from OFF to ON.
Resume operation of servo amplifier after checking the "[Md.26] Axis
operation status" of the connected servo amplifier by turning
bConnectCommand from OFF to ON.
System configuration
RD77MS
Servo amplifier
MR-J3(W)-_B/MR-J4(W)-_B
Disconnection (After Axis 5)
Axis 2
Axis 3
Axis 4
Axis 5
Axis 6
Axis 7
Axis 8
Axis 1
RD77MS16
ERR
RUN
AX1-16
\
\
\
\
\
\