9 COMMON FUNCTIONS
9.4 External Input Signal Select Function
9.4
External Input Signal Select Function
The "external input signal select function" sets the input type, input terminal, signal logic and input filter for each external input
signal of each axis (upper/lower stroke limit signal (FLS/RLS), near-point dog signal (DOG), and stop signal (STOP)).
The function enables the assignment of external input signal of each axis to any terminals of 20 points of the external input
connection connector on the Simple Motion module.
Input type/input terminal setting method
This function sets the input type and input terminal used for the external input signals used in each axis (upper/lower stroke
limit signal (FLS/RLS), near-point dog signal (DOG), and stop signal (STOP)). The setting method is shown below.
*1
The setting is not available in "[Pr.119] STOP signal selection". If it is set, the error "STOP signal selection error" (error code: 1AD3H)
occurs and the PLC READY signal [Y0] is not turned ON.
*2
The input terminals corresponding to the setting values are shown in the following table. "00H" is set as "No setting". (The control by the
external input signal is disabled.)
■
Point for input type/input terminal setting method
• Set the external command signal (DI) using "[Pr.95] External command signal selection". As for the terminal of the external
input connection connector of the Simple Motion module, DI number is defined to each SIN number in advance.
• When the input type of "[Pr.116] FLS signal selection" to "[Pr.119] STOP signal selection" is set with "0: Simple Motion
module", the external input connection connector terminal of the Simple Motion module is used in duplicate with the
external command signal (DI). The available range is shown below.
Setting item
Initial value
Setting details
[Pr.116]
FLS signal selection
0001H
■
Set with a hexadecimal.
[Pr.117]
RLS signal selection
0001H
[Pr.118]
DOG signal selection
0001H
[Pr.119]
STOP signal
selection
0002H
Setting value
Pin No.
Input terminal
Setting value
Pin No.
Input terminal
01H
1A1
SIN1
0BH
2A1
SIN11
02H
1A2
SIN2
0CH
2A2
SIN12
03H
1A3
SIN3
0DH
2A3
SIN13
04H
1A4
SIN4
0EH
2A4
SIN14
05H
1A5
SIN5
0FH
2A5
SIN15
06H
1B1
SIN6
10H
2B1
SIN16
07H
1B2
SIN7
11H
2B2
SIN17
08H
1B3
SIN8
12H
2B3
SIN18
09H
1B4
SIN9
13H
2B4
SIN19
0AH
1B5
SIN10
14H
2B5
SIN20
• RD77MS2: 1A1 to 1A5, 1B1 to 1B5
• RD77MS4/RD77MS8/RD77MS16: 1A1 to 1A5, 1B1 to 1B5, 2A1 to 2A5, 2B1 to 2B5
H _ _ _ _
Input type
Set the input type used as the external input signal.
0(0000H) : Simple Motion module
1(0001H) : Servo amplifier
2(0002H) : Buffer memory
15(000FH) : Invalid
*1
Input terminal
When the input type is set with "0: Simple Motion module",
set the input terminal of the external input connection connector
to be used.
The setting value can be set until "0AH" at RD77MS2 use.
The setting is not required when the value other than "0" is set.
(The setting is ignored.)
Summary of Contents for RD77MS16
Page 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Page 2: ......
Page 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Page 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Page 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Page 643: ......