5 PARAMETERS
5.2 Detailed list of parameters
PL09
LPWM
Magnetic pole
detection voltage
level
Set a direct current exciting voltage level during the magnetic pole detection.
If [AL. 32 Overcurrent], [AL. 50 Overload 1], or [AL. 51 Overload 2] occurs during the magnetic pole detection,
decrease the setting value.
If [AL. 27 Initial magnetic pole detection error] occurs during the magnetic pole detection, increase the setting
value.
Setting range: 0 to 100
30 [%]
PL17
LTSTS
Magnetic pole
detection - Minute
position detection
method - Function
selection
_ _ _ x
Response selection
The digit will be enabled when "Minute position detection method" is selected in [Pr. PL08].
Set a response of the minute position detection method.
When reducing a travel distance at the magnetic pole detection, increase the setting value.
For settings, refer to the following tables (Response of minute position detection method at magnetic pole
detection) for the setting value.
0h
_ _ x _
Load to motor mass ratio/load to motor inertia ratio selection
The digit will be enabled when "Minute position detection method" is selected in [Pr. PL08].
Select a load to mass of the linear servo motor primary-side ratio or load to mass of the direct drive motor
inertia ratio used at the minute position detection method. Set a closest value to the actual load.
For settings, refer to the load to following tables (Load to motor mass ratio/load to motor inertia ratio) for the
setting value.
0h
_ x _ _
For manufacturer setting
0h
x _ _ _
0h
Response of minute position detection method at magnetic pole detection
Load to motor mass ratio/load to motor inertia ratio
PL18
IDLV
Magnetic pole
detection - Minute
position detection
method -
Identification signal
amplitude
Set an identification signal amplitude used in the minute position detection method.
This parameter is enabled only when the magnetic pole detection is the minute position detection method.
However, when "0" is set, the amplitude will be 100%.
Setting range: 0 to 100
0 [%]
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]
Setting value
Response
_ _ _ 0
_ _ _ 1
_ _ _ 2
_ _ _ 3
_ _ _ 4
_ _ _ 5
_ _ _ 6
_ _ _ 7
Low response
Middle response
Setting value
Response
_ _ _ 8
_ _ _ 9
_ _ _ A
_ _ _ B
_ _ _ C
_ _ _ D
_ _ _ E
_ _ _ F
Middle response
High response
Setting value
10 times or less
_ _ 0 _
_ _ 1 _
_ _ 2 _
_ _ 3 _
_ _ 4 _
_ _ 5 _
_ _ 6 _
10 times
20 times
30 times
40 times
50 times
60 times
_ _ 7 _
70 times
Load to motor mass ratio/load to
motor inertia ratio
Setting value
80 times
_ _ 8 _
_ _ 9 _
_ _ A _
_ _ B _
_ _ C _
_ _ D _
_ _ E _
90 times
100 times
110 times
120 times
130 times
140 times
_ _ F _
150 times or more
Load to motor mass ratio/load to
motor inertia ratio