4 STARTUP
4.1 Switching power on for the first time
129
4
When you use an option and peripheral equipment (200 V class)
■
When you use a regenerative option for 5 kW or less servo amplifiers
• The lead wire between P+ terminal and D terminal should not be connected.
• The regenerative option wire should be connected between P+ and C terminal.
• Twisted wires should be used.
Page 341 Connection of regenerative option
■
When you use a regenerative option for 7 kW or more servo amplifiers
• For 7 kW servo amplifiers, the lead wire of the built-in regenerative resistor connected to P+ terminal and C terminal should
not be connected.
• The regenerative option wire should be connected between P+ and C terminal.
• Twisted wires should be used.
Page 341 Connection of regenerative option
■
When you use a brake unit and power regeneration converter for 5 kW or more servo
amplifiers
• For 5 kW servo amplifiers, the lead wire between P+ terminal and D terminal should not be connected.
• For 7 kW servo amplifiers, the lead wire of the built-in regenerative resistor connected to P+ terminal and C terminal should
not be connected.
• Wires of a brake unit or power regeneration converter should be connected to P+ terminal and N- terminal.
Page 366 FR-RC-(H) power regeneration converter
• Twisted wires should be used when wiring is over 5 m and equal to or less than 10 m using a brake unit.
■
When you use a power regeneration common converter
• For 5 kW or less servo amplifiers, the lead wire between P+ terminal and D terminal should not be connected.
• For 7 kW servo amplifiers, the lead wire of built-in regenerative resistor connected to P+ terminal and C terminal should not
be connected.
• The wire of power regeneration common converter should be connected to P4 terminal and N- terminal.
CV-(H) power regeneration common converter
■
When you use a power factor improving DC reactor
• The power factor improving DC reactor should be connected between P3 and P4.
Page 407 Power factor improving
*1 Always disconnect between P3 and P4 terminals.
When you use an option and peripheral equipment (400 V class)
■
When you use a regenerative option for 3.5 kW or less servo amplifiers
• The lead wire between P+ terminal and D terminal should not be connected.
• The regenerative option should be connected to P+ terminal and C terminal.
• Twisted wires should be used.
Page 341 Connection of regenerative option
■
When you use a regenerative option for 5 kW or more servo amplifiers
• For 5 kW or 7 kW servo amplifiers, the lead wire of the built-in regenerative resistor connected to P+ terminal and C
terminal should not be connected.
• The regenerative option should be connected to P+ terminal and C terminal.
• Twisted wires should be used.
Page 341 Connection of regenerative option
*1
Power factor improving
DC reactor
Servo amplifier
P3
P4