368
11 OPTIONS AND PERIPHERAL EQUIPMENT
11.4 FR-RC-(H) power regeneration converter
■
400 V class
*1 When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain removed, the FR-RC-
H will not operate.
*2 For the servo amplifier of 5 kW and 7 kW, be sure to disconnect the lead wire of built-in regenerative resistor, which is connected to P+
and C terminals. For the servo amplifier of 11 kW to 22 kW, do not connect a supplied regenerative resistor to the P+ and C terminals.
*3 If disabling ALM (Malfunction) output with the parameter, configure up the power supply circuit which switches off the magnetic contactor
after detection of alarm occurrence on the controller side.
*4 Between P3 and P4 is connected by default. When using the power factor improving DC reactor, remove the short bar between P3 and
P4. Additionally, a power factor improving DC reactor and power factor improving AC reactor cannot be used simultaneously.
Page 407 Power factor improving DC reactors
*5 For the power supply specifications, refer to the following.
Page 30 Servo amplifier standard specifications
*6 Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1). Configure up the circuit which shuts off main circuit power with external circuit
at EM1 (Forced stop 1) off.
*7 When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
*8 This diagram shows sink I/O interface. For source I/O interface, refer to the following.
*9 The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they can be
configured by one.
*10 For selection of power factor improving AC reactors, refer to "Power Regeneration Converter FR-RC Instruction Manual (IB(NA)66330)".
P3 P4
C
N-
P+
N/-
P/+
*4
RD
SE
MC
MCCB
*7
RX
R
SX
S
TX
T
R/L1
S/L2
T/L3
B
C
EM1
DICOM
CN3
DOCOM
ALM
CN3 24 V DC
*9
RA
B
C
FR-RC-H
ALM
RA
MC
MC
SK
L11
L21
L1
L2
L3
*2
A
B
C
*8
*8
24 V DC
*9
Power
supply
*5
Power factor
improving AC reactor
*10
Servo amplifier
Forced stop 1
*6
Malfunction
*3
5 m or shorter
Lady
Alarm output
RDY output
Phase detection
terminals
*1
Power regeneration converter
FR-RC-H
Operation
ready
OFF
ON
Forced stop 1
*6
Step-down
transformer
Summary of Contents for MELSERVO-J4 series
Page 2: ......
Page 605: ...APPX Appendix 6 EC declaration of conformity 603 A ...
Page 638: ...636 APPX Appendix 14 Encoder output pulse setting method MEMO ...
Page 645: ......