11 OPTIONS AND PERIPHERAL EQUIPMENT
11.5 FR-CV-(H) power regeneration common converter
373
11
Connection diagram
In this configuration, only the STO function is supported. The forced stop deceleration function is not
available.
■
200 V class
When using the servo amplifier of 7 kW or less, be sure to disconnect the wiring of built-in regenerative
resistor (3.5 kW or less: P+ and D, 7 kW: P+ and C).
*1 Configure a sequence that will shut off main circuit power in the following.
An alarm occurred at FR-CV or servo amplifier.
EM1 (Forced stop 1) is enabled.
*2 For the servo amplifier, configure a sequence that will switch the servo-on after the FR-CV is ready.
*3 Configure a sequence that will make a stop with the emergency stop input of the controller if an alarm occurs in the FR-CV. When the
controller does not have an emergency stop input, use the forced stop input of the servo amplifier to make a stop as shown in the
diagram.
*4 When using FR-CV, always disconnect wiring between P3 and P4 terminals.
*5 Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1).
*6 When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
*7 The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they can be
configured by one.
MC
MCCB
R/L11
3-phase
200 V AC
to
230 V AC
S/L21
T/L31
S2/L22
R2/L12
T2/L32
FR-CVL
MC
RA2
RA1
EM1 OFF
ON
*1
MC
SK
RA1
*3
EM1
R2/L1
S2/L2
N/L-
*2
P24
SD
RDYB
RDYA
SE
P/L+
T2/L3
R/L11
S/L21
T/MC1
*1
L11
L21
P4
N-
U
V
W
EM1
*1*5
U
V
W
CN2
FR-CV
Servo motor
Servo amplifier
Servo
system controller
*4
*6
DICOM
B
C
A
RA1
24 V DC
*7
24 V DC
*7
DOCOM
ALM
RA2
24 V DC
*7
Summary of Contents for MELSERVO-J4 series
Page 2: ......
Page 605: ...APPX Appendix 6 EC declaration of conformity 603 A ...
Page 638: ...636 APPX Appendix 14 Encoder output pulse setting method MEMO ...
Page 645: ......