11 OPTIONS AND PERIPHERAL EQUIPMENT
11.2 Regenerative options
MR-J4-500GF(-RJ) or less/MR-J4-350GF4(-RJ) or less
Always remove the wiring from across P+ to D and fit the regenerative option across P+ to C. G3 and G4 are thermal sensor's
terminals. Between G3 and G4 is opened when the regenerative option overheats abnormally.
*1 When using the MR-RB50, MR-RB5N, MR-RB51, MR-RB3M-4, MR-RB3G-4, or MR-RB5G-4, forcibly cool it with a cooling fan (1.0 m
3
/
min or more, 92 mm × 92 mm).
*2 When the ambient temperature is more than 55
and the regenerative load ratio is more than 60% in MR-RB30, MR-RB31, MR-RB32,
and MR-RB3N, forcefully cool the air with a cooling fan (1.0 m
3
/min or more, 92 mm × 92 mm). A cooling fan is not required if the
ambient temperature is 35
or less. (A cooling fan is required for the shaded area in the following graph.)
*3 Make up a sequence which will switch off the magnetic contactor when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120 V AC/DC
Maximum current: 0.5 A/4.8 V DC
Maximum capacity: 2.4 VA
D
P+
C
G4
G3
C
P
Regenerative option
5 m or less
Servo amplifier
Always remove the lead from across P+ to D.
*3
Cooling fan
*1*2
100
60
0
0
Ambient temperature [°C]
35
55
A cooling fan is
not required.
A cooling fan is required.
Load ratio [%]