16. Appendix
370
Make settings in the Select Parameter Category form (Fig. 16.7) as shown below.
[1] Select Transfer all selected parameters under the Select parameter transfer options.
[2] Select Controller basic unit dependent parameters transferred under Controller basic unit transmit options.
[3] Select “I/O”, “Common for All Axes”, “Others” and “Manufacturer Inside” in “Basic Setting”.
Select “I/O System Device” in addition when controller is XSEL-RA/SA, RAX/SAX or RAXD/SAXD.
After completing the above settings, click the OK button.
Parameter transfer will start.
Fig. 16.7 Transfer of Actuator Non-specific Parameters
After performing this procedure, always write the parameters to the flash ROM and reset software.
Since the data specific to each axis of the actuator has not been set, an error may be detected after power
reconnection or software reset. Even if an error is detected, perform the next step as it is.
[3]
[1]
[2]
Summary of Contents for IA-101-TT-USB
Page 2: ......
Page 4: ......
Page 8: ......
Page 50: ...1 Before You Begin 42 1 4 Connection to Controller Fig 1 48 X SEL K J Type Controller ...
Page 52: ...1 Before You Begin 44 Figure shows example of TT Fig 1 50 Table Top Actuator TT TTA ...
Page 53: ...1 Before You Begin 45 Fig 1 51 X SEL KX JX Type Controller ...
Page 62: ...1 Before You Begin 54 Fig 1 60 ASEL Type Controller USB Cable ...
Page 63: ...1 Before You Begin 55 Fig 1 61 PSEL Type Controller USB Cable ...
Page 189: ...9 Symbol Edit Window 181 ...
Page 251: ...13 How to Reset an Absolute Encoder 243 Fig 13 38 Arm Length 120 Reference Position ...
Page 386: ...16 Appendix 378 ...
Page 391: ......