ESIE15-08B
|
Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
19/07/16
Page 95
Daikin Altherma Monobloc CA
10. Power the Daikin Altherma Monobloc CA.
11. Measure the voltage across connector X60A: pin 1-3; compare the measured voltage with the expected voltage.
12. In case no voltage is measured across connector X60A: pin 1-3; do following checks:
13. Is PCB1 powered?, if not check power supply.
14. Is connector S60 plugged in PCB1?, if not plug in S60.
15. Is 5 VDC measured across connector S60: pin 4-3?, if not replace PCB1, refer to
"Replacing the PCB1 main" on page 119
.
-
In case all 3 checks above are OK but still no voltage is measured between X17: pin 1-3, replace the pressure sensor
S1NPH, refer to
"Replacing the pressure sensor S1NPH" on page 130
.
I
NFORMATION
The pressure sensor connector must be plugged into X60A on PCB1.
-5.1
-0.5
0
0.5
1
1.5
2
2.5
3
3.5
4
0
5.1
10.2
15.3
20.4
25.5
30.6
35.7
40.8
45.9
51.0
Detected Pressure
P
H
(kg/cm
2
)
P
H
= 1.38V
H
-0.69
V
H
: Output Voltage (High Side) V
DC
Output Voltage (V
H
, V
L
)
High Pressure (P
H
)
+5V
Red
S60
GND
Black
White
High pressure sensor
Microcomputer
A/D input
Measure DC voltage here
Outdoor unit PCB1 board
1
2
3
4