ESIE15-08B
|
Part 2. Troubleshooting
4. Component checklist - Water Circuit
Page 78
19/07/16
Daikin Altherma Monobloc CA
2.
Recover the refrigerant.
3.
Refer to the nameplate for the correct charge. If less than the indicated charge is recovered, a pressure test must be
performed.
4.
Pressurize the refrigerant circuit with Nitrogen at 40 bar.
5.
Check the pressure after 30 minutes.
6.
Decrease of nitrogen pressure and increase of water pressure indicates a leak of the plate type heat exchanger.