ESIE15-08B
|
Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
Page 100
19/07/16
Daikin Altherma Monobloc CA
10. While listening to the 4-way valve, place a round permanent magnet on the core of the solenoid valve. If you do not hear the
4-way valve switching, it must be replaced, refer to
"Replacing the 4-way valve" on page 127
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the hydrobox top plate assembly, refer to
"Removing the hydrobox top plate assembly" on page 110
4.
Remove the hydrobox front plate, refer to
"Removing the hydrobox front plate" on page 111
.
5.
Remove the top plate, refer to
"Removing the top plate" on page 112
6.
Remove the front plate assembly, refer to
"Removing the front plate assembly" on page 113
.
7.
Switch on the Daikin Altherma Monobloc CA via the user interface, start heating operation.
8.
Measure the voltage on connector S80: pin1 - 3. If the measured voltage does not range 220-240 VAC, unplug connector S80
and measure the voltage directly on the PCB2 connector S80: pin1 - 3.
- If the voltage, measured directly on the PCB does not range 220-240 VAC, replace PCB1, refer to
.
- If the voltage, measured directly on the PCB does range 220-240 VAC, replace the 4-way valve coil, refer to
.
9.
Unplug connector S80 from the inverter PCB2 and measure the resistance of the 4-way valve coil. If the measured resistance
does not range 1000 - 2000
Ω
, replace the 4-way valve coil, refer to
"Replacing the 4-way valve" on page 127
.
10. Switch on the Daikin Altherma Monobloc CA via the user interface, start cooling operation on the user interface.
If the temperature after the plate type heat exchanger rises, the control of the 4-way valve is wrong, update the software.
1.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
2.
Slide a magnet over the front and the rear of the 4-way valve body and sense the attraction of the magnet to determine the
valve position.
3.
If the magnet is attracted in positions A,A’ or B-B’, the 4-way valve is OK; if the magnet is attracted in positions C,C’ the 4-way
valve must be replaced,
"Replacing the 4-way valve" on page 127
.
Electrical check
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.
Determine the position of the 4-way valve