2.25. “HC-00” – Domestic hot water temperature error
2.26. “H0-00” – Voltage/current sensor problem
Trigger
Effect
Reset
Abnormal value detected (open or short
circuit) for DHW tank thermistor.
Unit will keep operating.
Auto reset when problem is solved.
Possible cause
Check
Corrective action
Faulty DHW tank thermistor R5T.
Check thermistor R5T (see page 70).
Replace thermistor R5T when required
(see page 124).
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
Faulty wiring between outdoor unit - Con-
trol box - DHW tank.
Check wiring (power supply, connections
between PCB’s, ...).
Adjust wiring when required.
Trigger
Effect
Reset
Faulty power supply conditions are
detected before or right after compressor
start-up.
•
Supplied voltage is too high or too
low?
•
Compressor current doesn’t run
when te compressor is started.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty compressor.
Check compressor (see page 91).
Check compressor connection and wiring.
Check expansion valve operation (liquid
back issue).
Check refrigerant charge (see page 106)
+ check for leaks.
Replace the compressor when required.
(see page 125).
Investigate the reason of breakdown.
Replace expansion valve when required
(see page 131).
Fix the possible leak.
Faulty outdoor inverter PCB.
Check outdoor inverter PCB (see
page 101).
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Adjust the power to the outdoor inverter
PCB.
Replace outdoor inverter PCB when
required (see page 122).
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).