ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
19/07/16
Page 25
Daikin Altherma Monobloc CA
2.14. “EC-00” – Domestic hot water temperature error
2.15. “E1-00” – Outdoor unit PCB abnormality
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB (see
page 131) when alive led is not blinking in
regular intervals (see page 119).
Faulty 4-way valve coil/ wire harness.
Check 4-way valve coil/ wire harness (see
page 99).
Replace 4-way valve coil/ wire harness
when required (see page 127).
Faulty 4-way valve body
Check 4-way valve body (see page 99).
Replace 4-way valve body when required
(see page 127).
Refrigerant shortage.
Check for refrigerant shortage (see
page 106).
Perform leak test.
If charge is lower than indicated on
name-plate, check for leaks and recharge
unit with correct amount of refrigerant.
Refrigerant contaminated
Check quality of the refrigerant
Replace refrigerant when required.
Make sure your refrigerant system is dry
and clean before charging!
Faulty stop valve
Check stop valves.
Replace stop valve when required.
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
Trigger
Effect
Reset
Water tank thermistor detects temperature
above 89°C.
Unit will continue operating.
Auto-reset when trouble is solved.
Possible cause
Check
Corrective action
Increased water temp by external heat
source (solar panel).
Check if another heat source is installed
on the same water circuit.
Correct hydraulic field circuit. Refer to the
Installer Reference Guide.
Faulty water tank thermistor R5T.
Check water tank thermistor (see
page 70).
Replace thermistor R5T when required
(see page 124).
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
Trigger
Effect
Reset
Outdoor main PCB detects that EEPROM
is abnormal.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).