
ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
19/07/16
Page 29
Daikin Altherma Monobloc CA
2.22. “E9-00” – Expansion valve abnormality
2.23. “F3-00” – Discharge pipe temperature control
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Faulty or disturbance of the power supply.
(Imbalance > 10%) Power drop.
Short circuit.
Check if the power supply is conform with
regulations. No fluctuations in frequency.
Adjust power supply when required.
Power reset via outdoor unit.
Trigger
Effect
Reset
1. No continuity of expansion valve.
2. Minimum expansion valve opening and
suction superheat < 4 K and discharge
superheat < 5 K.
Unit will stop operating.
Manual reset via user interface (power
reset might be necessary in case no com-
mon power supply was cause).
Possible cause
Check
Corrective action
Faulty or disturbance of the power supply.
(Imbalance > 10%) Power drop.
Short circuit.
Check if the power supply is conform with
regulations. No fluctuations in frequency.
Adjust power supply when required.
Power reset via outdoor unit.
Faulty expansion valve.
Check expansion valve (see page 97).
Replace expansion valve when required.
Faulty thermistor on outdoor.
Check thermistors on outdoor (see
page 70).
Replace thermistors when required (see
page 124).
Faulty pressure sensor / outdoor main
PCB.
Check pressure sensor (see page 94).
Replace the pressure sensor (see
page 130) or outdoor main PCB (see
page 119) when required.
Wet operation.
Check for wet operation. (Wet operation
can be detected by checking the suction
superheat. If the suction superheat is 0°C
then liquid refrigerant is returning to the
compressor.)
In case wet operation was detected con-
firm the cause:
• Refrigerant
overcharge.
•
Faulty expansion valve.
External factor (e.g. electrical noise)
(cause when error is reset after power
reset, and error happens again after
awhile).
Check for source which could cause elec-
trical interference.
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Trigger
Effect
Reset
1. Discharge temperature > 110°C for 15
minutes.
2. Discharge temperature > 125°C.
Unit will stop operating.
Manual reset via user interface -> only
possible when below 95°C.
Possible cause
Check
Corrective action
Refrigerant shortage (incorrect charge /
leakage blockage).
Check for refrigerant shortage (see
page 106).
Perform leak test.
Repair the leak and charge the correct
amount of refrigerant (check nameplate).
Faulty thermistor R2T.
Check thermistor R2T (see page 88).
Replace thermistor R2T when required
(see page 124).