ESIE15-08B
|
Part 2. Troubleshooting
3. Symptom based troubleshooting
Page 56
19/07/16
Daikin Altherma Monobloc CA
3.6. Water leakage or water release via the water pressure relieve valve
Root cause category: installation
User interface - thermostat
sensor value not representing
room temperature.
Bad location of thermostat
sensor (external influence) in
case of room thermostat con-
trol (setting [C-07]=2).
Check if user interface is
mounted in the correct position
to measure the correct room
temperature.
Correct the position of the user
interface for more accurate
room temperature measure-
ment.
Root cause category: component - electrical
Leaving water thermistor devi-
ation causes incorrect temper-
ature control.
• Deviation
of
thermistor
(lower temperature
measured than actual).
•
Bad contact between
sensor and pipe.
Check leaving water thermis-
tor (see page 70).
Replace leaving water ther-
mistor or hydro PCB A1P.
Deviation of domestic hot
water tank thermistor.
(Remark: only valid for inaccu-
rate domestic hot water tem-
perature control.)
• Deviation
of
thermistor.
•
Bad contact between
sensor and pipe.
Check thermistor DHW tank
thermistor (see page 70).
Replace DHW tank thermistor
or hydro PCB A1P.
User interface (A2P) - thermo-
stat sensor has incorrect read-
ing of room temperature.
Deviation of user interface
room temperature sensor.
Compare temperature meas-
ured by user interface with
actual room temperature.
In case of deviation the room
temperature offset can be
adjusted through setting
[2-0A].
Possible failures
Root cause
Check
Corrective action
Root cause category: installation
Drain connection of water
safety valve leaking.
Bad connection between unit
drain pipe and field drain pipe.
Check the drain connection of
the water safety valve.
Correct the drain connection if
required.
Drain of bottom drain plate not
well connected.
Bad connection of bottom
drain plate and field drain con-
nection.
Check the drain connection
between the bottom drain
plate and the field drain.
Correct the drain connection if
required.
Leakage of drain valve.
Valve not completely closed.
Check if drain valve is closed.
Close the drain valve.
Root cause category: component - mechanical
Expansion vessel not pressu-
rized.
Component failure.
Check expansion vessel.
Replace expansion vessel.
Safety valve blocked.
Component failure.
Check safety valve.
Replace safety valve.
Safety valve leaking.
Component failure.
Check safety valve.
Replace safety valve.
Leakage of drain valve.
Component failure.
Check drain valve.
Replace drain valve.
Domestic hot water tank leak-
age.
Component failure.
Check tank visually for leak-
ages.
Repair leakages. If not possi-
ble, complete unit has to be
replaced.
Air Purge leakage.
Component failure.
Check air purge valve for leak-
ages.
Replace air purge valve.
Possible failures
Root cause
Check
Corrective action