ESIE15-08B
|
Part 3. Repair
2. Unit specific repair procedures Monobloc CA
Page 122
19/07/16
Daikin Altherma Monobloc CA
2.2.5. Replacing the PCB2 inverter
2.2.5.1 Preliminary actions
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the switch box, refer to
"Replacing the switch box" on page 117
.
4.
Remove the PCB assembly main, refer to
"Replacing the PCB1 main" on page 119
2.2.5.2 Procedure
Removal
1.
Loosen and remove the 3 screws (1).
2.
Unplug Faston plugs U (2), V (3) and W (4) from the PCB2 assembly inverter (7).
3.
Unplug connectors S70 (5) and S80 (6) from the PCB2 assembly inverter (7).
4.
Remove the PCB2 assembly (7).
5.
Loosen and remove the 8 screws (8).
6.
Separate PCB2 (9) from the heatsink (10).
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.