ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
Page 32
19/07/16
Daikin Altherma Monobloc CA
2.27. “H1-00” – Optional temperature sensor error (indoor ambient)
2.28. “H3-00” – High pressure switch abnormality
2.29. “H6-00” – Malfunction of position detection sensor
Trigger
Effect
Reset
Optional thermistor detects an abnormal
value (open or short circuit).
Unit will keep operating.
Auto reset when problem is solved.
Possible cause
Check
Corrective action
Faulty option thermistor R6T.
Check thermistor R6T (see page 70).
Replace thermistor R6T when required
(see page 124).
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
Trigger
Effect
Reset
High pressure switch is activated when
compressor is off.
Unit stops operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty high pressure switch.
Check high pressure switch (see
page 96).
Replace the high pressure switch (see
page 129).
Stop valve is closed.
Check if stop valve is open.
Open stop valve when required.
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Trigger
Effect
Reset
The compressor fails to start in about 15
seconds after the compressor run com-
mand signal is sent.
Unit will stop operating.
First 7 times: auto restart.
8th time: Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty compressor.
Check compressor (see page 91).
Check compressor connection and wiring
(see page 144).
Check expansion valve operation (liquid
back issue).
Check refrigerant charge (see page 106)
+ check for leaks.
Replace the compressor when required.
(see page 125).
Investigate the reason of breakdown.
Replace expansion valve when required.
Fix the possible leak.
Faulty outdoor inverter PCB.
Check outdoor inverter PCB (see
page 101).
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Adjust the power to the outdoor inverter
PCB.
Replace outdoor inverter PCB when
required (see page 122).