ESIE15-08B
|
Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
Page 92
19/07/16
Daikin Altherma Monobloc CA
6.
Remove the front plate assembly, refer to
"Removing the front plate assembly" on page 113
.
7.
Open the compressor insulation.
8.
Switch on the unit and measure the U,V,W inverter voltages. All voltages must be identical, if not, replace the inverter PCB2,
refer to
"Replacing the PCB2 inverter" on page 122
.
9.
Switch off the Daikin Altherma Monobloc CA via the user interface.
10. Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
11. Disconnect the Faston connectors U, V and W from the compressor.
12. Measure the compressor motor windings U-V, V-W and U-W; all measurements must read 1.7
Ω
.
13. Megger the compressor using 500 or 1000 V DC, the insulation must be higher than 3 M
Ω
.
14. Replace the compressor if the windings and/or insulation measurements fail, refer to
"Replacing the compressor" on page 125
15. Run the compressor and measure the current in each phase; the current for each phase should be identical and between 4 and
7 A. When the current exceeds 10 A during normal operation, it could indicate internal wear of the compressor. In that case it
can be decided to preventively replace the compressor, refer to
"Replacing the compressor" on page 125
.
I
NFORMATION
Note the position of the cables on the compressor wire terminals to allow identical wiring during reinstallation.