ESIE15-08B
|
Part 3. Repair
1. General Repair procedures
19/07/16
Page 105
Daikin Altherma Monobloc CA
Part 3. Repair
1. General Repair procedures
1.1. Refrigerant handling procedures
•
Make sure the applied pressure is never higher than the unit design pressure as indicated on the nameplate.
•
Work according the F-gas regulation and/or local regulations.
•
Make sure the correct amount (f additional where required) of refrigerant is charged after repair.
•
Make sure to use the appropriate equipment and tools according to the refrigerant and unit type.
•
Charge non-azeotropic refrigerant (e.g. R-410A) always in a liquid state.
•
Make sure to use a digital scale (no charging cylinder).
•
Execute correct vacuum drying procedure after repair work:
-
-0,1 MPa / -760 mmHg / -750 Torr for at least 1 hour.
-
Use both gas and liquid pipe connection.
-
Use related field setting where necessary.