ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
19/07/16
Page 27
Daikin Altherma Monobloc CA
2.18. “E5-00” – Compressor motor lock
2.19. “E6-00” – Compressor startup defect
Bad contact through pressure sensor
cable.
Check if pressure sensor connector X17A
is properly connected to the outdoor PCB
board A1P.
Connect or replace sensor cable when
required.
Faulty pressure sensor.
Check the pressure sensor (see page 94).
Replace the pressure sensor when
required (see page 130).
Abnormal drop of low pressure, caused by
inadequate refrigerant, abnormal refriger-
ant piping system or faulty electronic
expansion valve.
Check for possible blockage. (blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage
(remark: this is not valid for the expansion
valve))
Replace the blocked part.
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Trigger
Effect
Reset
The motor rotor does not rotate when the
compressor is energized.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Refrigerant circuit is clogged (HP - LP
> 0,26 MPa).
Check for possible blockage (blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage
(remark: this is not valid for the expansion
valve)).
Replace the blocked part.
Faulty compressor.
Check compressor (see page 91).
Check compressor connection and wiring.
Check expansion valve operation (liquid
back issue).
Check refrigerant charge (see page 106)
+ check for leaks.
Replace the compressor when required.
(see page 125).
Investigate the reason of breakdown.
Replace expansion valve when required
(see page 131).
Fix the possible leak.
Stop valve is closed.
Check if stop valve is open.
Open stop valve when required.
Faulty inverter voltage output.
Check if inverter output voltages have
same amplitude.
Replace outdoor inverter PCB when
required (see page 122).
Compressor turned off too fast.
Wait for guard timer to pass (3 min).
Faulty outdoor inverter PCB.
Check outdoor inverter PCB (see
page 101).
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Adjust the power to the outdoor inverter
PCB.
Replace outdoor inverter PCB when
required (see page 122).
Faulty expansion valve.
Check expansion valve (see page 97).
Replace expansion valve when required
(see page 131).
Faulty 4-way valve.
Check 4-way valve (see page 99).
Replace 4-way valve when required (see
page 127).
Trigger
Effect
Reset
System detects that the current waveform
to the compressor has an abnormality, 16
times in 5 min.
Unit will stop operating.
Manual restart via user interface.