ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
Page 48
19/07/16
Daikin Altherma Monobloc CA
2.65. “89-03” – Plate heat exchanger warning during defrost
Trigger
Effect
Reset
Te is too low during defrost.
Defrost cycle is interrupted but unit will
continue operation.
Auto-reset when problem is solved.
Warning might result to 89-01 error if it
occurs 3 times.
R2T measures < 6°C during defrost.
Units stops after guard timer of compres-
sor.
PHE outlet temperature increases, auto-
matic restart.
Possible cause
Check
Corrective action
Faulty outlet backup heater thermistor.
Check outlet backup heater thermistor.
Replace outlet backup heater thermistor
when required (see page 124).