Part 2. Troubleshooting
2. Error code based troubleshooting
19/07/16
Page 35
Daikin Altherma Monobloc CA
2.35. “J7-00” – Malfunction of intermediate heat exchanger thermistor
2.36. “J8-00” – Malfunction of liquid pipe thermistor
2.37. “LC-00” – Transmission system abnormality
Trigger
Effect
Reset
Intermediate heat exchanger thermistor
detects an abnormal value (open or short
circuit).
Unit stops operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty intermediate heat exchanger ther-
mistor (R5T).
Check thermistor R5T (see page 88).
Replace thermistor R5T when required
(see page 124).
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Trigger
Effect
Reset
Liquid pipe thermistor detects an abnor-
mal value (open or short circuit).
Unit stops operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty intermediate heat exchanger ther-
mistor (R6T).
Check thermistor R6T (see page 88).
Replace thermistor R6T when required
(see page 124).
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Trigger
Effect
Reset
No transmission between outdoor main
PCB and outdoor inverter PCB.
Unit stops operating.
Auto-reset.
Possible cause
Check
Corrective action
Internal wiring is not OK.
Check if wiring between PCB’s is correct
(refer to wiring diagram).
Correct wiring.
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Faulty outdoor inverter PCB.
Check outdoor inverter PCB (see
page 101).
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Adjust the power to the outdoor inverter
PCB.
Replace outdoor inverter PCB when
required (see page 122).