ESIE15-08B
|
Part 2. Troubleshooting
4. Component checklist - Water Circuit
19/07/16
Page 69
Daikin Altherma Monobloc CA
4.2. Booster heater E4H
Not applicable
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the front panel of the control box.
4.
Check electrical connections of the tank. Refer to “Installation manual of the tank”.
5.
Check if contactor K3M has tripped.
6.
Power the daikin altherma Monobloc CA and activate domestic hot water.
7.
Measure the voltage on connector X4M pin 1 - neutral and measure the voltage on X4M pin 3 - neutral, if no 230 VAC is present
in both measurements, clixon Q2L/Q3L tripped. -> reset Q2L/Q3L.
Technical specification
Description
The booster heater is a single element heater.
The booster heater is used to assist the heat
pump system to heat the domestic hot water.
Location
Wiring diagram
Control Box
Unit
Check procedure
Mechanical check
Electrical check
I
NFORMATION
If Q2L/Q3L trips again, it is required to determine the root cause of the problem because something is overloading the
electrical circuit or creating a short circuit.
I
NFORMATION
If 1 or more checks fail, replace the booster heater.
X1M
X8M
X2M
K2A
K3M
K1A
A4P
F2B
X4M