Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
19/07/16
Page 89
Daikin Altherma Monobloc CA
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the hydrobox top plate assembly, refer to
"Removing the hydrobox top plate assembly" on page 110
4.
Remove the front panel, refer to
"Removing the front plate assembly" on page 113
5.
Locate the thermistor and check if thermal contact with the piping or ambient is ensured.
The Table 2-4 on page 90 must be used to compare the measured resistance with the correct resistance for the measured
temperature with a contact thermometer.
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
3.
Remove the front panel, refer to
"Removing the front plate assembly" on page 113
4.
From the Table 2-4 on page 90, select the thermistor that must be checked.
5.
Measure the temperature of the thermistor using a contact thermometer.
6.
Unplug the connector from the appropriate PCB and measure the resistance between the pins listed in Table 2-5 on page 90.
-
Compare the measured resistance with the range determined by the lower and higher temperature in Table 2-5 on
page 90.
7.
If the measured resistance does not match the listed value, the thermistor must be replaced, refer to
E.g. thermistor R3T:
•
Measured temperature with contact thermometer: 23.1°C.
•
Unplug the sensor and measure the resistance between S90: 1-2: 21.86 k
Ω
.
•
The resistance values are defined by Table 2-5 on page 90:
-
Resistance at 23°C: 21.85 k
Ω
.
-
Resistance at 24°C: 20.90 k
Ω
.
Check procedure
C
AUTION
If the platework of the
Daikin Altherma Monobloc CA is bent (e.g. when replacing a thermistor), chances are the
platework no longer aligns correctly with the hea
t exchanger. This will increase the risk of ice build-up.
Mechanical check
Electrical check
I
NFORMATION
If a thermistor check fails, replace the thermistor.
W
ARNING
: R
ISK
OF
F
IRE
•
When reconnecting a connector to the PCB, do not apply force or damage the connector or the connector pins on
the PCB.
I
NFORMATION
All thermistors have a tolerance of 5%.