ESIE15-08B
|
Part 2. Troubleshooting
4. Component checklist - Water Circuit
19/07/16
Page 85
Daikin Altherma Monobloc CA
9.
Using a contact thermometer, measure the temperature at the 3-way valve Domestic Hot Water exit and at the Space Heating
exit; the Domestic Hot Water exit must have the same temperature as the 3-way valve input, the Space Heating exit must have
a much lower temperature.
10. Activate Space Heating.
11. Measure the voltage on connector X1M/N and X1A: pin 2 on PCB A4P; if no 230 VAC is present, replace PCB A5P.
12. Using a contact thermometer, measure the temperature at the 3-way valve Domestic Hot Water exit and at the Space Heating
exit; the Space Heating exit must have the same temperature as the 3-way valve input, the Domestic Hot Water exit must have
a much lower temperature.
13. If one or both checks above are not OK, remove the 3-way valve motor from the 3-way valve.
14. Set the 3-way valve manually in the Domestic Hot Water position.
15. Using a contact thermometer, measure the temperature at the 3-way valve Domestic Hot Water exit and at the Space Heating
exit; the Domestic Hot Water exit must have the same temperature as the 3-way valve input, the Space Heating exit must have
a much lower temperature.
16. Set the 3-way valve manually in the Space Heating position.
17. Using a contact thermometer, measure the temperature at the 3-way valve Domestic Hot Water exit and at the Space Heating
exit; the Domestic Hot Water exit must have the same temperature as the 3-way valve input, the Space Heating exit must have
a much lower temperature.
18. If one or both checks above are not OK, the 3-way valve body must be replaced.
19. If both checks above are OK, the 3-way valve motor must be replaced.
X20A
X26A