ESIE15-08B
|
Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
Page 90
19/07/16
Daikin Altherma Monobloc CA
•
The measured value 21.86 k
Ω
is inside the range, thermistor R3T passes the check.
Table 2-4: Thermistors ERLQ04-08
Table 2-5: Thermistor resistance / temperature characteristics
I
NFORMATION
The user interface “6.1. Sensor Information” allows to monitor most thermistors.
If the measured resistance of the thermistor matches the temperature measured with the contact thermometer but the
temperature for the corresponding thermistor is not correct on the user interface display, replace outdoor unit main PCB
(see
"Replacing the PCB1 main" on page 119
).
Thermistor
Processed on PCB
Connector: pin
Description
R1T PCB1
S90:5-6
Discharge
R2T
PCB1
S90:3-4
Heat exchanger
R3T PCB1
S90:1-2
Air
T °C
k
Ω
T °C
k
Ω
T °C
k
Ω
T °C
k
Ω
T °C
k
Ω
-20
197.81
0
65.84
20
25.01
40
10.63
60
4.87
-19
-18
-17
-16
-15
-14
-13
-12
-11
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
1
2
3
4
5
6
7
8
9
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
21
22
23
24
25
26
27
28
29
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
41
42
43
44
45
46
47
48
49
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
61
62
63
64
65
66
67
68
69
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
-10
111.99
10
39.96
30
16.10
50
7.18
70
3.44
-9
-8
-7
-6
-5
-4
-3
-2
-1
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
11
12
13
14
15
16
17
18
19
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
31
32
33
34
35
36
37
38
39
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
51
52
53
54
55
56
57
58
59
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
71
72
73
74
75
76
77
78
79
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
80
2.47