ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
Page 38
19/07/16
Daikin Altherma Monobloc CA
2.42. “L8-00” – Electronic thermal overload
2.43. “PJ-00” – Defective capacity setting
2.44. “UA-00” – Indoor-Outdoor PCB combination
Trigger
Effect
Reset
When compressor overload (except dur-
ing startup) is detected.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Refrigerant circuit is clogged.
Check for possible blockage (blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage
(remark: this is not valid for the expansion
valve)).
Replace the blocked part.
Refrigerant overcharge.
Check for refrigerant overcharge.
Charge the system with correct refrigerant
charge.
Faulty compressor.
Check compressor (see page 91).
Check compressor connection and wiring.
Check expansion valve operation (liquid
back issue).
Check refrigerant charge (see page 106)
+ check for leaks.
Replace the compressor when required.
(see page 125).
Investigate the reason of breakdown.
Replace expansion valve when required
(see page 131).
Fix the possible leak.
Faulty outdoor inverter PCB.
Check outdoor inverter PCB (see
page 101).
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Adjust the power to the outdoor inverter
PCB.
Replace outdoor inverter PCB when
required (see page 122).
Trigger
Effect
Reset
Outdoor main PCB detects a defective
capacity in EEPROM.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Positions of PCB dip switches are not OK.
Check if dip switches are set to default
(OFF) position.
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Trigger
Effect
Reset
System detects combination mismatch
between outdoor main PCB and hydro
PCB or outdoor inverter PCB.
Unit will stop operating.
Auto-reset.
Possible cause
Check
Corrective action
Wrong unit combination.
Check combination database.
Correct installation.
Wrong field setting for compressor type.
Check setting [E-01].
Check setting [E-01] to correct value.