ESIE15-08B
|
Part 2. Troubleshooting
3. Symptom based troubleshooting
Page 64
19/07/16
Daikin Altherma Monobloc CA
3.16. Water volume/flow related
Possible failures
Root cause
Check
Corrective action
The water flow is to low (7H
error)
Shut off valve are closed.
Check if shut off valves are com-
pletely open.
Open shut of valves if required.
Water filter is dirty.
Check the water filter.
Clean water filter when required.
Air in the system.
Perform an air purge, refer to
Installer Reference Guide.
Water pressure is >1bar.
Check the water pressure on the
manometer.
Add water when required until
water pressure is +/- 2 bar.
Expansion vessel is broken.
Check the expansion vessel.
Replace expansion vessel when
required.
The resistance in the water cir-
cuit is too high for the pump.
Check ESP curves.
Adjust water circuit when
required.
Flow sensor is broken.
Check flow sensor and flow sen-
sor connector to PCB board.
Replace flow sensor of flow sen-
sor harness when required.
Water volume is too low
Check if the water volume is cor-
rect, refer to installer reference
guide
Add water when required.