Table 2-2: Thermistor resistance / temperature characteristics (type 1)
Table 2-3: Thermistor resistance / temperature characteristics (type 2)
R2T
A1P
X15M: 1-2
1
Outlet water after backup heater
R3T
A1P
X7A: 1-2
1
Refrigerant liquid
R4T
A1P
X8A: 1-2
1
Inlet water
R5T
A1P
X2M: 3-4
2
Domestic hot water tank
R6T
A1P/A4P
X5M: 5-6 / X2M:1a-2a
1
External indoor or outdoor ambient
T °C
k
Ω
T °C
k
Ω
T °C
k
Ω
T °C
k
Ω
T °C
k
Ω
-20
197.81
0
65.84
20
25.01
40
10.63
60
4.87
-19
-18
-17
-16
-15
-14
-13
-12
-11
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
1
2
3
4
5
6
7
8
9
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
21
22
23
24
25
26
27
28
29
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
41
42
43
44
45
46
47
48
49
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
61
62
63
64
65
66
67
68
69
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
-10
111.99
10
39.96
30
16.10
50
7.18
70
3.44
-9
-8
-7
-6
-5
-4
-3
-2
-1
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
11
12
13
14
15
16
17
18
19
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
31
32
33
34
35
36
37
38
39
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
51
52
53
54
55
56
57
58
59
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
71
72
73
74
75
76
77
78
79
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
80
2.47
T °C
k
Ω
-20
2534
-15
1877
-10
1404
-5
1059
0
806.5
5
618.9
10
478.8
15
373.1
20
292.9
25
231.4
30
184.1
35
147.4
40
118.7
45
96.13
50
78.29