Part 2. Troubleshooting
5. Component checklist - Refrigerant Circuit
Page 104
19/07/16
Daikin Altherma Monobloc CA
5.
Check fuse FU2 on PCB2, replace if blown.
6.
Check if connector S70 is plugged into PCB2.
7.
Power the outdoor unit.
8.
Check power supply on X1M, the measured voltage must be 180 - 240 VAC.
Fan does not rotate
1.
Confirm via D-checker that fan gets on ON signal.
2.
Measure the voltage on S70: pin 4 - 7.
If the measured voltage does not equal 300 VDC +/- 30 VDC, disconnect S70 and check the inverter PCB2, refer to
.
If the inverter PCB2 check is OK, replace the fan motor, refer to
"Replacing the DC fan motor assembly" on page 116
.
If the inverter PCB2 check is not OK, replace the inverter PCB2, refer to
.
3.
Measure the voltage on S70: pin 4 - 3.
If the measured voltage does not equal 15 VDC, disconnect S70 and measure again on the PCB connector.
If the voltage measured on the PCB connector equals 15 VDC, replace the fan motor, refer to
If the voltage measured on the PCB connector does not equal 15 VDC, replace the inverter PCB2, refer to
Fan rotates for a short time
1.
Confirm via D-checker that fan gets on ON signal.
2.
Measure the voltage on S70: pin 4 - 7.
If the measured voltage does not equal 300 VDC +/- 30 VDC, disconnect S70 and check the inverter PCB2, refer to
.
If the inverter PCB2 check is OK, replace the fan motor, refer to
"Replacing the DC fan motor assembly" on page 116
.
If the inverter PCB2 check is not OK, replace the inverter PCB2, refer to
.
3.
Measure the voltage on S70: pin 4 - 3.
If the measured voltage does not equal 15 VDC, disconnect S70 and measure again on the PCB connector.
If the voltage measured on the PCB connector equals 15 VDC, replace the fan motor, refer to
If the voltage measured on the PCB connector does not equal 15 VDC, replace the inverter PCB2, refer to
4.
Measure the voltage on S70: pin 4 - 2.
If the voltage measured equals 0 VDC, replace the inverter PCB2, refer to
.
If the voltage measured is between 0 - 10 VDC, replace the fan motor, refer to
"Replacing the DC fan motor assembly" on
5.
Switch off the unit via the user interface.
6.
Manually revolve the fan propeller slowly 1 turn (in about 4 seconds) and check that 4 pulses of 5 VDC are measured on
S70: pin 2 - 1.
If no pulses are detected, replace the fan motor, refer to
"Replacing the DC fan motor assembly" on page 116
.
If pulses are detected, replace the PCB1 main, refer to
"Replacing the PCB1 main" on page 119
.