ESIE15-08B
|
Part 1. Introduction
3. General operation of Daikin Altherma CA low temperature heat pump
Page 14
19/07/16
Daikin Altherma Monobloc CA
When the unit starts operation, following behaviour occurs:
When space heating thermo ON is decided and pump is working on
∆
T control (default 5°C):
•
The inverter water pump will gradually adjust its speed to reach and maintain the required delta T (this is the water temperature
difference between the leaving water and entering water (adjustable by setting)).
•
The inverter compressor (after pressure equalisation) will gradually adjust its speed to reach and maintain the required water
temperature.
When the domestic hot water function is activated, the 3-way valve will switch over to the domestic hot water tank and space
heating side is closed. Domestic hot water and space heating cannot be active simultaneously. The 3-way valve will switch back
to space heating when domestic hot water setpoint is reached or when running timers are finished (refer to the Installer Reference
Guide for more details).
When the unit receives a thermo OFF signal:
•
The compressor will stop its operation.
•
The water pump will operate for some more minutes and eventually stop or start sampling.
H
2
O pump
Remocon
“ON”
Decide thermo
“ON”
Thermo
“OFF”
Sampling(*)
Sampling(*)
Pressure equalisation
(EV = 480 pls)
Compressor
Inverter control
1 min.
~ 3 min.
ON
t
OFF
ON
OFF
(*) H
2
O pump sampling operation only in case of leaving water temperature control (not in case of room temperature control).