ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
Page 24
19/07/16
Daikin Altherma Monobloc CA
2.11. “C0-02” – Flow switch error
2.12. “C4-00” – Refrigerant liquid thermistor R3T abnormality
2.13. “EA-00” – 4-way valve malfunction
Trigger
Effect
Reset
Flow switch warning triggered too often.
Unit detects flow when pump is not run-
ning.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty flow switch.
Check flow switch (see page 83).
Replace flow switch when required.
Water flow caused by external pump
Check if another (external) pump is
installed in the same water circuit.
Correct hydraulic field circuit. Refer to
Installer Reference Guide.
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
Faulty wire harness
Check the wire harness and the connec-
tion to hydro PCB A1P.
Replace the wire harness when required.
Trigger
Effect
Reset
Thermistor detects an abnormal value
(open or short circuit).
Unit will stop operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty refrigerant liquid thermistor R3T.
Check refrigerant liquid thermistor R3T
(see page 70).
Replace refrigerant liquid thermistor R3T
when required (see page 124).
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
Trigger
Effect
Reset
After an operation of 5 min, following con-
dition occurs over 10 min:
Heating: Hydro-box heat exchanger tem-
perature minus outlet water temperature <
-10°C.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Faulty outlet water heat exchanger ther-
mistor.
Check outlet water heat exchanger ther-
mistor (see page 70).
Replace thermistor when required (see
page 124).
Faulty refrigerant liquid side thermistor.
Check refrigerant liquid side thermistor
(see page 70).
Replace thermistor when required (see
page 124).
Replace hydro PCB A1P when required.