ESIE15-08B
|
Part 2. Troubleshooting
2. Error code based troubleshooting
19/07/16
Page 45
Daikin Altherma Monobloc CA
2.57. “7H-05” – Water flow abnormality during space heating operation
2.58. “7H-06” – Water flow abnormality during defrost/cooling operation
2.59. “8F-00” – Backup heater outlet water temperature error during domestic hot
water operation
Possible cause
Check
Corrective action
See possible cause for 7H-01.
Focus error handling on DHW circuit.
-
-
Trigger
Effect
Reset
Water flow abnormality detected mainly
during space heating operation.
Unit will stop operating, after some time it
will automatically try to start operating
again.
Manual reset via user interface.
Possible cause
Check
Corrective action
See possible cause for 7H-01.
Focus error handling on DHW circuit.
-
-
Trigger
Effect
Reset
Water flow abnormality detected mainly
during defrost/cooling operation.
Unit will stop operating, after some time it
will automatically try to start operating
again.
Manual reset via user interface.
Possible cause
Check
Corrective action
See possible cause for 7H-01.
Focus error handling on cooling circuit.
-
-
Trigger
Effect
Reset
Outlet backup heater thermistor detects
temperature above 75°C during domestic
hot water operation.
Unit will stop operating.
Manual reset via user interface.
Possible cause
Check
Corrective action
Increased water temp by external heat
source.
Check if another heat source is installed
on the same water circuit.
Correct hydraulic field circuit. Refer to the
Installer Reference Guide.
Faulty outlet backup heater thermistor.
Check outlet backup heater thermistor
(see page 70).
Replace outlet backup heater thermistor
when required.
Faulty backup heater contactors (stick-
ing).
Check backup heater control contactors
(see page 66).
Replace the contactor(s) when required.
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.